PM170207000





GX KIT-1200 LED 4500 IC-E3/S 850 BN25-SPECIAL ITEM
Description
The LED replacement kit for MAX brings a longer product lifetime, a greener profile and low maintenance.
To upgrade the MAX T8 version to LED with new certificate, you have to replace the gear tray, the diffuser, the clips and if it is an emergency version the battery with connection.
All necessary parts are included in the replacement kit; the gear tray, the diffuser, the clips and if it is an emergency version the battery with connection.
- Barcode
7054130896418
- Stock code
C
Technical description
- Technical data
-
EX gas classification
II 2G Ex eb mb op is IIC T5 Gb
-
EX dust classification
II 2D Ex tb IIIC T81°C Db
-
IP classification
66/67
-
Minimum ambient temperature (ºC)
-20
-
Maximum ambient temperature (°C)
40
- Dimensions
-
Net weight (kg)
8,7
-
Gross weight (kg)
8,66
- Body
-
Body material
Aluminium/zinc treated steel
-
Colour of body
White
-
Body colour code
White
- Optic
-
Optic
Clear
-
Material of diffuser
Polycarbonate
-
Lightdistribution Up/Down
5/95
- Electrical data
-
Minimum Voltage -10% (VAC)
230
-
Maximum voltage +10% (VAC)
230
-
Minimum frequency -5% (Hz)
50
-
Maximum frequency +5% (Hz)
60
-
Minimum voltage in DC
-
-
Maximum voltage in DC
-
-
Total consumption (W)
47
-
Number of luminaires on a 10A MCB type B (80% load)
37
-
Number of luminaires on a 10A MCB type C (80% load)
37
-
Number of luminaires on a 16A MCB type B (80% load)
60
-
Number of luminaires on a 16A MCB type C (80% load)
60
-
Leakage Current (mA)
0,8
- Ballast/Driver
-
Type of ballast/driver
IC driver technology with emergency
-
Number of ballast/driver
4
-
Wiring Accessories
Integrated emergency with battery box
- Emergency
-
Type of emergency
Standard battery backup
-
Duration in battery mode (hrs)
3 hours
-
Output in battery mode (%)
9
- Light data
-
Light source
LED
-
Colour rendering and colour temperature
CRI>80, 5000K
-
System Lumen Out
4190
-
System Lumen/Watt
89
-
Rated system lifetime at Ta 45°C
100.000h
-
Rated system lifetime at Ta 25°C
110.000h
-
Rated system lifetime at Ta max°C
83.000h
- Termination
-
Type of cable gland
M25-Nickel plated brass
-
Number of cable glands
2
-
Minimum cable diameter
10
-
Maximum cable diameter
18
-
Type of blind-plug
M25-Nickel plated brass
-
Number of blind plugs
2
- Remarks
-
Remarks
GX LED KIT consists of Complete Gear Tray with battery, Diffuser, Locking bracket for diffuser, Glands/Blinds M25 Nickel plated and screws for mounting of KIT to GX main body..See Service Manual for furher details.